74
Coding in the delivered condition
Possible change
23:4
Stop temperature differ-
ential for central heating
backup: 4 K.
Switching output
sS
is
switched OFF when the
temperature at sen-
sor
/
falls below the
stop point. The stop point
is the sum of the temper-
ature at sensor
aÖ
and
the value selected for the
stop temperature differ-
ential.
23:2
to
23:30
Stop temperature differen-
tial for central heating
backup is adjustable from 1
to 29 K
24:40
Start temperature for the
thermostat function
40 °C.
Start temperature for the
thermostat function
≤
stop temperature for the
thermostat function:
Thermostat function e.g.
for reheating. Switching
output
sS
is switched ON
when the temperature at
sensor
/
falls below the
start temperature for the
thermostat function.
Start temperature for
thermostat function >
stop temperature for ther-
mostat function:
Thermostat function e.g.
for utilising excess heat.
Switching output
sS
is
switched ON when the
temperature at sen-
sor
/
exceeds the start
temperature for the ther-
mostat function.
24:0
to
24:100
Start temperature for ther-
mostat function is adjusta-
ble from 0 to 100 K
Code 2
Solar/Group "4"
(cont.)
5692 843 GB