101
Dis-
played
fault
code
Const.
Weath.-
comp.
System char-
acteristics
Cause
Measures
bd
X
Control mode
without remote
control
Communica-
tion error,
remote con-
trol Vitotrol
heating circuit
2 (with mixer)
Check connec-
tions, lead, coding
address "A0" and
remote control set-
tings (see
page 132)
bE
X
Control mode
without remote
control
Communica-
tion error,
remote con-
trol Vitotrol
heating circuit
3 (with mixer)
Check connec-
tions, lead, coding
address "A0" and
remote control set-
tings (see
page 132)
bF
X
Control mode
Incorrect
LON commu-
nication mod-
ule
Replace the LON
communication
module
C1
X
X
Control mode
Communica-
tion error
extension
EA1
Check electrical
connections
C2
X
X
Control mode
Communica-
tion error,
solar control
module or
Vitosolic
Check solar control
module or
Vitosolic
C3
X
X
Control mode
Extension
AM1 commu-
nication error
Check electrical
connections
C4
X
X
Control mode
Communica-
tion error,
Open Therm
extension
Check Open
Therm extension
C5
X
X
Control mode,
max. pump
speed
Communica-
tion error, var-
iable speed
internal pump
Check the setting
of coding address
"30"
Troubleshooting
Fault codes
(cont.)
5692 843 GB