65
Select
"Boiler"
for weather-compensated control units (see page 55).
Select
"2"
for constant temperature control units (see page 55).
Coding
Coding in the delivered condition
Possible change
01:1
Single boiler system (only
for constant temperature
control units)
01:2
Multi-boiler system with
Vitotronic 300-K
04:1
Minimum burner pause
subject to the boiler load
(specified by boiler cod-
ing card)
04:0
Minimum burner pause set
permanently (specified by
boiler coding card)
06:...
Maximum limit of the
boiler water temperature,
defaulted in °C by the
boiler coding card
06:20
to
06:127
Maximum limit of the boiler
water temperature within
the ranges specified by the
boiler
0d:0
Do not adjust
0E:0
Do not adjust
13:1
Do not adjust
14:1
Do not adjust
15:1
Do not adjust
21:0
No service interval (hours
run) selected
21:1
to
21:100
The number of hours run
before the burner should
be serviced is adjustable
from 100 to 10,000 h
One adjusting step
≙
100 h
23:0
No time interval for
burner service
23:1
to
23:24
Interval adjustable from 1
to 24 months
24:0
No
"Service"
display
24:1
"Service"
display (the
address is automatically
set and must be manually
reset after a service has
been carried out)
28:0
No burner interval igni-
tion
28:1
to
28:24
Time interval adjustable
from 1 to 24 h. The burner
is force-started once every
30 s (only when operating
with LPG)
Code 2
Boiler/Group "2"
5692 843 GB