68
Coding in the delivered condition
Possible change
62:2
Circulation pump with
2 min run-on time after
cylinder heating
62:0
Circulation pump without
run-on
62:1
to
62:15
Run-on time adjustable
from 1 to 15 min
63:0
Without auxiliary function
for DHW heating (only for
constant temperature
control units)
63:1
Auxiliary function: 1 x daily
63:2
to
63:14
Every 2 days to every 14
days
63:15
2 x daily
65:0
Do not adjust!
67:40
For solar DHW heating:
Set DHW temperature
40 °C. Reheating is sup-
pressed above the selec-
ted set temperature
(DHW heating blocked by
the boiler).
67:0
to
67:95
Set DHW temperature
adjustable from 0 to 95 °C
(limited by boiler-specific
parameters)
6C:100
Set speed; internal circu-
lation pump with DHW
heating 100 %
6C:0
to
6C:100
Set speed adjustable from
0 to 100 %
6F:...
Maximum output for
DHW heating in %, speci-
fied by the boiler coding
card
6F:0
to
6F:100
Max. output during DHW
heating adjustable from
min. output to 100 %
71:0
DHW circulation pump:
"ON" in accordance with
the time program (only for
weather-compensated
control units)
71:1
"OFF" during DHW heating
to the first set value
71:2
"ON" during DHW heating
to the first set value
72:0
DHW circulation pump:
"ON" in accordance with
the time program (only for
weather-compensated
control units)
72:1
"OFF" during DHW heating
to the second set value
72:2
"ON" during DHW heating
to the second set value
73:0
DHW circulation pump:
"ON" in accordance with
the time program (only for
weather-compensated
control units)
73:1
to
73:6
"ON" from once per hour
for 5 min up to 6 times per
hour for 5 min during the
time program
73:7
Constantly "ON"
Code 2
DHW/Group "3"
(cont.)
5692 843 GB