63
Coding in the delivered condition
Possible change
7F:1
Detached house (only for
weather-compensated
control units)
7F:0
Apartment building
Separate adjustment of
holiday program and time
program for DHW heating,
as option
80:6
A fault message is dis-
played, providing a fault
is active for at least 30 s
80:0
Immediate fault message
80:2
to
80:199
The minimum fault duration
before a fault message is
issued is adjustable from
10 s to 995 s; one step
≙
5 s
81:1
Automatic summer/win-
ter time changeover
81:0
Manual summer/winter
time changeover
81:2
Use of the radio clock
receiver (automatic recog-
nition)
81:3
With LON communication
module: The control unit
receives the time
82:0
Operation with natural
gas
82:1
Operation with LPG (only
adjustable if coding
address 11:9 has been
set)
86:0
Do not adjust
87:0
Do not adjust
88:0
Temperature displayed in
°C (Celsius)
88:1
Temperature displayed in
°F (Fahrenheit)
8A:175
Do not adjust!
8F:0
All control elements
active
8F:1
All control elements locked
out
8F:2
Only standard settings can
be controlled
90:128
Time constant for calcu-
lating the adjusted out-
side temperature 21.3 h
90:1
to
90:199
Fast (low values) or slow
(high values) matching of
the flow temperature, sub-
ject to the set value when
the outside temperature
changes;
1 step
≙
10 min
Code 2
General/Group "1"
(cont.)
5692 843 GB