72
Pumps and other components
Pump/component
Parameter
Setting
Heating circuit pump
"System definition"
Ó
"System scheme 7000"
■ With heating circuit A1/
HC1 (for heating circuit
without mixer)
or
■ With heating circuit M2/
HC2 (for heating circuit
with mixer)
DHW circulation pump
Extended menu:
"Time program DHW cir-
culation"
Set time program
Circulation pump for
DHW reheating
"External heat source"
Ó
"Enable external heat
source 7B00"
"1"
"External heat source"
Ó
"Enable external heat
source for DHW heating
7B0D"
"1"
In conjunction with the
primary store system:
■ Cylinder primary pump
■ 2-way motorised valve
"System definition"
Ó
"System scheme 7000"
With DHW heating
"DHW"
Ó
"Cylinder primary pump
enable 601F"
"1"
"DHW"
Ó
"Operating mode cylin-
der primary pump 6020"
Setting according to type of
cylinder primary pump
Mixer extension kit for
heating circuit M2/HC2
"System definition"
Ó
"System scheme 7000"
With heating circuit M2/
HC2
Note
Set rotary switch S1 in the
extension kit to "2" (see ex-
tension kit installation in-
structions).
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5782 176 GB