73
Pump/component
Parameter
Setting
Remote control
For the heating/cooling cir-
cuit:
"Heating circuit 1"
Ó
"Remote control 2003"
or
"Heating circuit 2"
Ó
"Remote control 3003"
"1"
Note
Set code on the Vitotrol to
assign heating circuits:
H1/HC1 for heating circuit
1
H2/HC2 for heating circuit
2
(see "Vitotrol" installation in-
structions).
Vitocom 100, type GSM
"System definition"
Ó
"Vitocom 100 7017"
"1"
Extension
"System definition"
Ó
"External extension
7010"
■
"1"
EA1
■
"2"
AM1
■
"3"
EA1 and AM1
Note
For parameters for external
functions, see the following
table.
External functions
External functions
Parameter
Setting
External demand
If applicable
"Internal hy-
draulics"
Ó
"Flow temperature for ex-
ternal demand 730C"
Set flow temperature
for external demand
External starting of the com-
pressor; mixer in control
mode or OPEN
"System definition"
Ó
"Effect of external demand
on heat pump/heating cir-
cuits 7014"
"0"
to
"7"
(Observe parameter
"Flow temperature
for external demand
730C"
)
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5782 176 GB
Service