29
A
AVI PCB (see page 43)
F101 MCB/fuse 1.0A (slow)
B
Switching module and power supply
for instantaneous heating water
heater (see from page 50)
C
Power supply 230 V~ (see
page 46)
F1 MCB/fuse 6.3 A (slow)
D
Luster terminals (see page 37)
X1 Terminals for earth conductor of
all
associated system compo-
nents
X2 Terminals for neutral conductor
of
all
associated system com-
ponents
E
Controller and sensor PCB (see
page 39)
F
Main PCB (see page 29)
F3 MCB/fuse 6.3 A (slow)
G
Expansion PCB on main PCB (see
page 33)
Internal unit: Main PCB (function components 230 V~)
Information regarding the connection
values
■ The specified output is the recommen-
ded connected load.
■ The total output of all components con-
nected directly to the heat pump con-
trol unit must not exceed 1000 W (e.g.
pumps, valves, message facilities,
contactors).
If the total output is < 1000 W, the indi-
vidual rating of a component (e.g.
pump, valve, message facility, contac-
tor) can be greater than specified.
However, the breaking capacity of the
corresponding relay must not be
exceeded.
■ The specified current indicates the
max. switching current of the switching
contact (observe the total current of
5 A).
Set the required parameters during com-
missioning; see from page 68.
Installation sequence
Electrical connections
(cont.)
5782 176 GB
Installation