14
B
Gravel bed as condensate soak-
away
C
Concrete foundations (see technical
guide)
D
Drainage pipe DN 100 (only with
entries below ground level)
E
Rubber mounts (supplied)
Note
We recommend letting condensate drain
away freely (without condensate pipe).
Wall mounting
Installation must
only
be performed with
the bracket set suitable for wall mounting
(accessory).
Separate installation instructions
Installing the internal unit
!
Please note
Avoid damaging the appliance
during transportation.
Never
put weight on top of the
appliance.
Installation room requirements
!
Please note
The installation room must be dry
and free from the risk of frost.
Safeguard ambient temperatures
between 0 and 35 °C.
!
Please note
Avoid the risk of explosion due to
dust, gases and vapours
in the installation room.
Minimum room volume (to EN 378):
Type AWB/AWB-
AC
Minimum room
volume in m
3
201.B04
2.7
201.B07
4.8
201.B10
6.7
201.B13
6.7
201.C10
6.7
201.C13
6.7
Installation sequence
Installing the external unit
(cont.)
5782 176 GB