47
■ In conjunction with on-site energy con-
sumption (use of power generated by
the PV system to meet own require-
ments):
Note
During the power-OFF period, it is
not possible to operate the compres-
sor with power generated on site.
■ Protect the power supply to the heat
pump control unit with a fuse of 16 A
(max.).
■ For accessories and external compo-
nents that are not connected to the
heat pump control unit, connect the
power supply with the same phase as
the heat pump control unit, ideally
using the same fuse/MCB.
Connection to the same fuse/MCB
provides additional safety when the
power is switched off. Observe the
power consumption of the connected
consumers.
Heat pump control unit power supply (230 V~)
X40
A
N
?
L1
N
?
L1
F1 T6,3 AH
1/N/PE
230 V/50 Hz
Note
This supply must never be blocked.
■ Max. fuse rating 16 A
■ Standard tariff (no optional economy
tariff with power-OFF)
■ Recommended power cable:
3 x 1.5 mm
2
(5 x 1.5 mm
2
with power-
OFF)
Installation sequence
Power supply
(cont.)
5782 176 GB
Installation