"Relay" sub-menu
Note
Here, the relays can be activated at random.
Some actuators may still be switched ON when this menu is called up.
!
Please note
Unintentional conflicting operating situations can be created using
"manual control" (e.g. "
E heating 1: On
" and "
secondary pump: Off
").
This can lead to equipment damage.
For this reason, first set
all
actuators to "
Off
" during every operating pro-
cedure, then set the
required
actuators to "
On
".
!
Please note
If the intervals between manually switching the compressor off and on
again are too short, the compressor and the full wave soft starter may be
damaged.
After switching the compressor off, wait for at least 10 minutes before
switching it on again.
Menu item
&
"
Device settings
"
&
"
Contractor level
"
&
"
Manual control
"
&
"
Relay
"
–
The "
RESET
" key switches all
relays OFF, that are currently
switched ON.
–
Select a relay by pressing
x
and
y
, then switch the relay
with the keys "
ON
" and "
OFF
".
&
"
OK
"
"Mixer" sub-menu
The motors for the internal and external mixers (max. 3) can be manually
adjusted here.
Valve position
in %
Three-way valve
Heating/DHW
(internal)
Three-way mixer
Heating circuit 2
(mixer circuit)
Three-way mixer
"Natural cooling"
0
Heating
closed
closed
50
Heating/DHW
—
—
100
DHW heating
open
open
Menu item
&
"
Device settings
"
&
"
Contractor level
"
&
"
Manual control
"
Manual control of relays and mixers
(cont.)
132
Control settings
55
92
968
GB
Summary of Contents for VITOCAL 200-G
Page 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Page 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Page 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Page 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Page 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Page 206: ...206 5592 968 GB ...
Page 207: ...207 5592 968 GB ...