Compressor power supply
A
Terminals at the control module
Recommended core cross-section:
1.5 mm
2
Note
The upstream fuses must have Z
characteristics.
Instantaneous heating water heater power supply
A
Terminals in the control panel
Max. fuse rating 16 A
Recommended core cross-section:
2.5 mm
2
The three heating elements are
switched by inserting jumpers across
X60.8, X60.9 and X60.10 in star for-
mation and must be connected to N.
Power supply 400 V~, one tariff
&
One common power cable with a large cross-section up to the vicinity of the
heat pump.
&
The common power cable cannot be blocked. Selective blocking of the indivi-
dual power cables must take place downstream of the sub-distribution, which
means additional sub-distribution costs.
Adapt the cross-section of common power cable to the connected load of the
instantaneous heating water heater and the compressor. The connected load of
the control unit does not have to be taken into consideration.