Fault messages
Cause
Measures
EXT E heater
The flow temperature
does not rise; the in-
stantaneous heating
water heater may be
faulty
Check the high limit safety
cut-out and the heater ele-
ments; replace, if required
AC
Natural cooling
Faulty function
As part of the relay test (see
page 131), check the natural
cooling connection exten-
sion and the continuity to the
pumps
AD
Mixer
–
heating/
DHW
Mixer faulty
Check the mixer (see
page 110); replace, if re-
quired
AF
Cylinder primary
pump
Faulty cylinder primary
pump
Check the pump (see
page 110); replace, if re-
quired
B1
KM communica-
tion
Communication error,
programming unit
Check connections and re-
place the programming unit,
if required
BA
KM BUS
mixer HC 2
Communication fault
mixer HC 2
Check the extension kit con-
nections; start the extension
kit
BB
KM BUS
NC mixer
Communication fault
natural cooling mixer
BC
KM BUS
RC HC 1
Fault KM BUS remote
control; heating circuit 1
Check connections and
cables/leads
BD
KM BUS
RC HC 2
Fault KM BUS remote
control; heating circuit 2
C1
Power supply/
compressor
The compressor power
supply is not OK (e.g.
rotational direction,
asymmetrical, phase
failure). Compressor
fuse, main isolator,
phase monitor or motor
overload faulty
Check the power supply and
components; replace, if re-
quired
C4
Power-OFF con-
tact
Power-OFF contact en-
abled longer than 12 h
Check the Power-OFF con-
tact and replace if required
Control unit diagnostics
(cont.)
117
Troubleshooting
55
92
968
GB
Service
Summary of Contents for VITOCAL 200-G
Page 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Page 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Page 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Page 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Page 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Page 206: ...206 5592 968 GB ...
Page 207: ...207 5592 968 GB ...