3.
Switch ON the power.
Remedy any faults that may be sig-
nalled by the phase monitor (see
page 84) and re-check the rotating
field.
4. Isolate
the system from the power
supply and
safeguard against re-
connection
.
Without phase monitor installation
1.
Switch ON the power.
2.
Check rotating field of power sup-
ply connection and correct if
necessary.
3. Isolate
the system from the power
supply and
safeguard against re-
connection
.
4.
Fit strapping plug from pack to pos.
G
of the control module (see
page 19).
Making the electrical connections of the cylinder loading sys-
tem
Note
This connection must
only
be made if a
cylinder loading system
is used for
DHW heating.
Using a
directly
heated cylinder requires
no
additional pump.
Checking the rotating field of the power supply . . .
(cont.)
60
Installation sequence
55
92
968
GB