Note
This setting is only used if parameter set "
1
" (free parameters) has been
selected under "
Cooling mixer parameters
".
For function description see page 163.
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"NC mixer active zone"
(
%
/
5
)
or
"NC mixer dead zone"
(
=
/
0
)
Standard setting
Setting range
"
NC mixer active zone
"
4.0 K
2.0 to 40 K
"
NC mixer dead zone
"
1.0 K
0.5 to 3.0 K
Cooling mixer runtime
Note
This setting is only used if parameter set "
1
" (free parameters) has been
selected under "
Cooling mixer parameters
".
Setting of the time required by the servomotor of the cooling mixer for a
com-
plete
changeover from one operating state into another (90 degree movement).
Runtimes that are too short, can lead to the cooling mixer "Cycling".
Access
&
"
Device settings
"
&
"
Programming
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"Cooling mixer runtime"
(
m
/
l
)
Standard setting
0:10 min
Setting range
0:05 to
4:15 min
Active zone/dead zone natural cooling mixer
167
Heating circuit control settings
55
92
968
GB
Service
Summary of Contents for VITOCAL 200-G
Page 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Page 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Page 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Page 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Page 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Page 206: ...206 5592 968 GB ...
Page 207: ...207 5592 968 GB ...