HR Heating water return
(Multi-connect system)
HV Heating water flow
(Multi-connect system)
!
Please note
With
underfloor heating cir-
cuits
, there is a risk of building
damage through the screed
overheating if the control unit
fails.
Equip
underfloor heating cir-
cuits
with a temperature lim-
iter.
1.
Thoroughly flush the heating sys-
tem (particularly when connecting
to an existing system) and connect
the heating water flow and return in
accordance with the adjacent dia-
gram.
2.
Carry out a leak/tightness test.
Operating pressure:
3 bar
Max. test pressure:
4 bar
Making the electrical connections to external components
Note
The unit's external electrical connec-
tions are located together on the con-
trol panel in the top r.h. area of the
unit (see X60 on
B
in illustration on
page 54).
Sensor connections
With the exception of the outside tem-
perature sensor, we recommend the
use of screened cable (e.g. J-Y(St)Y,
2 x 0.8 mm, max. 10 m long).
Note
Never run LV cables immediately next
to 230/400 V cables.
For cable runs
>
10 m, use a larger
cross-section or terminate several
cores together.
Connecting the heating circuits
76
Installation sequence
55
92
968
GB
Summary of Contents for VITOCAL 200-G
Page 8: ...Certificates Declaration of conformity 201 Keyword index 202 Index cont 8 Index 5592 968 GB ...
Page 122: ...Main menu Information Menu structure overview information 122 Control settings 5592 968 GB ...
Page 187: ...Parts lists cont 187 Parts lists 5592 968 GB Service ...
Page 188: ...Parts lists cont 188 Parts lists 5592 968 GB ...
Page 189: ...Parts lists cont 189 Parts lists 5592 968 GB Service ...
Page 206: ...206 5592 968 GB ...
Page 207: ...207 5592 968 GB ...