53
Required heat pump parameters
"Output compressor stage 5030"
During commissioning, the heating output of the heat
pump
must
be set subject to type.
Type AWB/AWB-AC
201.B04
201.B05
201.B07
201.B10
201.C10
201.B13
201.C13
201.C16
"Output compressor stage 5030"
4 kW
5 kW
7 kW
10 kW
13 kW
16 kW
Required parameters for components connected on site
Parameters may need to be set subject to the type of
appliance, the selected system scheme and the acces-
sories used.
Overview of required parameters: See following chap-
ters.
Detailed explanations on parameters
"Vitotronic 200" service instructions
System scheme
Overview of all available system schemes
Component
System scheme
0
1
2
3
4
5
6
11
Heating circuit
A1/HC1
—
X
X
—
—
X
X
—
M2/HC2
—
—
—
X
X
X
X
—
DHW cylinder
X
—
X
—
X
—
X
—
Immersion heater
0
—
0
—
0
—
0
—
Heating water buffer cylinder
—
0
0
X
X
X
X
—
External heat generator
0
0
*1
0
*1
0
0
0
0
—
Instantaneous heating water heater
(type AWB-AC only)
X
X
X
X
X
X
X
—
Swimming pool
—
0
0
0
0
0
0
—
Cooling
(only type AWB-AC)
A1/HC1
—
0
0
—
—
0
0
—
M2/HC2
—
—
—
0
0
0
0
—
Separate cooling circuit
SKK
0
0
0
0
0
0
0
—
Electricity meter, 3-phase
0
0
0
0
0
0
0
0
Ventilation unit
0
0
0
0
0
0
0
0
X Component is selected.
0
Component may be added.
"System examples, heat pumps"
*1
Only in conjunction with a heating water buffer cylinder
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5700 542 GB