55
Parameters
Setting
Vitocom 100, type GSM/GSM2
"System definition"
Ó
"Vitocom 100 7017"
"1"
External extension
"System definition"
Ó
"External extension 7010"
"1"
EA1 extension
"2"
AM1 extension
"3"
EA1 and AM1 extensions
Note
Parameters for external functions: See
the following table.
Parameters for external functions
Parameter
Setting
External demand
If applicable
"Internal hydraulics"
Ó
"Flow temperature for external demand 730C"
Set flow temperature for external de-
mand
External starting of the compressor; mixer in control mode or OPEN
"System definition"
Ó
"Effect of external demand on heat pump/heating circuits
7014"
"0"
to
"7"
(Observe parameter
"Flow tempera-
ture for external demand 730C"
)
External changeover of the operating status of various system components
"System definition"
Ó
"System components for external changeover 7011"
"0"
to
"127"
"Operating status for external changeover 7012"
"0"
to
"3"
"Duration of external changeover 7013"
"0"
to
"12"
External blocking of compressor and pumps
"System definition"
Ó
"Effect of external blocking on pumps/compressor 701A"
"0"
to
"31"
External blocking of the compressor; mixer in control mode or CLOSED
"System definition"
Ó
"Effect of ext. blocking on heat pump/heating circuits 7015"
"0"
to
"8"
"Effect of external blocking on pumps/compressor 701A"
"0"
to
"31"
Type AWB-AC: Cooling function parameters
Parameters
Setting
"Cooling"
Ó
"Cooling function 7100"
"3"
"Cooling circuit 7101"
"1"
Heating circuit A1/HC1
"2"
Heating circuit M2/HC2
"4"
Separate cooling circuit SKK
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5700 542 GB