105
Parameters
Code
Delivered condition Commission-
ing
Maintenance/
service
"System components for external
changeover"
7011
0
"Operating status for external change-
over"
7012
2
"Duration of external changeover"
7013
8 h
"Effect of external demand on heat
pump/heating circuits"
7014
4
"Effect of ext. blocking on heat pump/
heating circuits"
7015
4
"Vitocom 100"
(only type GSM/GSM2)
7017
0
"Effect of external blocking on pumps/
compressor"
701A
0
"Common flow temperature sensor sys-
tem"
701B
0
"Number of lag heat pumps"
7029
0
Compressor
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
Service
"Enable compressor"
5000
1
"Enable use of compressor stage"
5012
15
"Output compressor stage"
5030
Rated heating output
according to type
plate
"Primary source output"
5043
Do not adjust
External heat generator
Parameter
Code
Delivered condition Commission-
ing
Maintenance/
Service
"Enable external heat source"
7B00
0
"Priority ext. heat source/Instant. heating
water heater"
7B01
1
"Dual mode temperature external heat
source"
7B02
100 (
≙
10 °C)
"Enable external heat source for central
heating"
7B0C
1
"Enable external heat source for DHW
heating"
7B0D
0
"Shutdown limit, heat pump dual mode"
7B0F
–
500 (
≙
–
50 °C)
"Enable boiler water temperature sen-
sor"
7B11
1
Commissioning/service reports
Control parameters report
(cont.)
5700 542 GB
Appendix