18
Connection to the external unit
C
D
C
D
4.
3.
2x
2.
Fig. 13
Example type AWB/AWB-AC 201.B04
C
Liquid line
D
Hot gas line
1.
Undo the side cover: See page 33.
2.
!
Please note
Contamination (e.g. metal swarf) or moisture
in the copper pipes of the refrigerant lines will
cause the appliance to malfunction.
Hold the pipe openings downwards or tempo-
rarily plug them.
Undo the nuts from connections
C
(liquid line) and
D
(hot gas line) of the refrigerant lines.
Type AWB/AWB-AC 201.B04:
Slide the nuts onto the refrigerant lines prepared on
site.
Type AWB/AWB-AC 201.B05 to B13, 201.C10 to
C16:
Replace nuts with union nuts supplied (internal
unit):
■
⅝
UNF for liquid line
■
⅞
UNF for hot gas line
3.
Flare the pipe ends.
4.
Secure the pipes.
Installation sequence
Connecting refrigerant lines
(cont.)
5700 542 GB
Installation