115
Type AWB/AWB-AC
201.C10
201.C13
201.C16
Cooling capacity data
to EN 14511
(A35/W18, 5 K spread)
Rated cooling capacity
kW
8.83
12.83
14.22
Fan speed
rpm
600
690
690
Power consumption
kW
1.98
3.45
4.23
Energy efficiency ratio EER in
cooling mode
4.46
3.72
3.43
Air intake temperature
Cooling mode (type AWB-AC)
■
Min.
°C
15
15
15
■
Max.
°C
45
45
45
Heating mode
■
Min.
°C
–
20
–
20
–
20
■
Max.
°C
35
35
35
Heating water
(secondary cir-
cuit)
Content (excl. expansion vessel) l
3.2
3.2
3.2
Minimum flow rate (must be
maintained)
l/h
1600
1600
1600
Minimum volume in the heating
system (cannot be fitted with
shut-off devices)
l
50
50
50
Max. external pressure drop
(RFH) at minimum flow rate
mbar
450
450
450
kPa
45
45
45
Max. flow temperature
°C
55
55
55
External unit electrical values
■
Rated voltage, compressor
3/N/PE 400 V/50 Hz
■
Max. operating current, com-
pressor
A
7.85
9.89
13.09
■
Starting current, compressor
A
10
10
10
■
Starting current, compressor
with stalled armature
A
16
16
16
■
MCB/fuse protection
A
16
16
16
■
IP rating
IP
X4
X4
X4
Internal unit electrical values
Heat pump control unit/PCB
■
Rated voltage, control
unit/PCB
1/N/PE 230 V/50 Hz
■
MCB/fuse protection, power
supply
1 x B16A
■
Internal fuse
6.3 A (slow)/250 V
Instantaneous heating water
heater
Only for type AWB-AC
■
Rated voltage
1/N/PE 230 V/50 Hz
3/N/PE 400 V/50 Hz
■
Heating output
kW
8.8
8.8
8.8
■
MCB/fuse protection, power
supply
3 x B16A
3 x B16A
3 x B16A
Specification
Specification
(cont.)
5700 542 GB
Appendix