114
Type AWB/AWB-AC
201.B04
201.B05
201.B07
201.B10
201.B13
Sound power of external unit
at rated
heating output
(measurements with reference to EN 12102/
EN ISO 9614-2)
Weighted total sound power level
■
At A7
±
3 K
/W55
±
5 K
dB(A)
60
62
62
62
63
■
At A7
±
3 K
/W55
±
5 K
in night mode dB(A)
58
58
58
60
60
Energy efficiency class
to EU
Regulation no. 811/2013
Heating, average climatic condi-
tions
■
Low temperature applications
(W35)
A
++
A
++
A
++
A
++
A
++
■
Medium temperature applica-
tions (W55)
A
+
A
+
A
+
A
++
A
+
400 V appliances
Type AWB/AWB-AC
201.C10
201.C13
201.C16
Heating output data
to EN 14511
(A2/W35)
Rated heating output
kW
7.57
9.06
11.2
Fan speed
rpm
600
690
690
Power consumption
kW
2.00
2.42
3.45
Coefficient of performance
ε
(COP) in heating mode
3.79
3.72
3.20
Output control
kW
2.73 to 10.92
3.30 to 12.29
—
Heating output data
to EN 14511
(A7/W35, 5 K spread)
Rated heating output
kW
10.16
12.07
15.5
Fan speed
rpm
600
690
690
Air flow rate
m
3
/h
3456
4217
4217
Power consumption
kW
2.00
2.57
3.76
Coefficient of performance
ε
(COP) in heating mode
5.08
4.69
4.11
Output control
kW
5.20 to 15.00
6.20 to 16.50
—
Heating output data
to EN 14511
(A
–
7/W35)
Rated heating output
kW
9.50
10.70
13.3
Power consumption
kW
3.06
3.69
5.12
Coefficient of performance
ε
(COP) in heating mode
3.10
2.90
2.59
Cooling capacity data
to EN 14511
(A35/W7, 5 K spread)
Rated cooling capacity
kW
9.14
10.75
11.85
Fan speed
rpm
600
690
690
Power consumption
kW
3.37
4.15
5.59
Energy efficiency ratio EER in
cooling mode
2.71
2.59
2.17
Output control
kW
1.96 to 9.85
2.14 to 11.45
—
Specification
Specification
(cont.)
5700 542 GB
Appendix