14
Transport
!
Please note
Impacts, compression and tensile loads can
cause damage to the outside panels of the
appliance.
Never
apply loads/weight to the top, front or
side panels of the appliance.
Installation room requirements
!
Please note
Unfavourable ambient conditions can lead to
malfunctions and appliance damage.
■
The installation room must be dry and free
from the risk of frost.
■
Ensure ambient temperatures between 0 and
35 °C.
Danger
Dust, gases and vapours can be damaging to
health and trigger explosions.
Avoid dust, gases and vapours in the installation
room.
Minimum room volume (to EN 378):
Type AWB/AWB-AC Minimum room volume in m
3
201.B04
2.7
201.B05
4.8
201.B07
4.8
201.B10
6.7
201.B13
6.7
201.C10
6.7
201.C13
6.7
201.C16
6.7
Minimum clearances
100
1000
100
A
B
Fig. 8
A
Cable entry <42 V
B
Cable entry 400 V~/230 V~,
>
42 V
Installation sequence
Installing the internal unit
5700 542 GB
Installation