87
Parameter
group
Parameter location
Description
Value
Commission-
ing
Mainte-
nance/
Service
Heating
Config./ Parameters/
Sensors/Sensors/Ambient
temperature
Outside temperature
averaging time
24 h
System/Heating circuits/
Pump circuit 1/Heating limit
day (requires service pass-
word)
Heating circuit 1
Heating limit day
Heating circuit 2
Heating limit day
Heating circuit 3
Heating limit day
19 °C
System/Heating circuits/
Pump circuit 1/Heating limit
night (requires service
password)
Heating circuit 1
Heating limit night
Heating circuit 2
Heating limit night
Heating circuit 3
Heating limit night
19 °C
System/Cylinder/Set value/
Heating limit day
Heating water buffer
cylinder Heating limit
day
20 °C
System/Cylinder/Set value/
Heating limit night
Heating water buffer
cylinder Heating limit
night
17 °C
System/Heating circuits/
Heating circuit1/Curve/Day
standard room temperature
Heating circuit 1 Day
standard room tem-
perature
Heating circuit 2 Day
standard room tem-
perature
Heating circuit 3 Day
standard room tem-
perature
20 °C
System/Heating circuits/
Heating circuit1/Curve/
Night standard room tem-
perature
Heating circuit 1
Night standard room
temperature
Heating circuit 2
Night standard room
temperature
Heating circuit 3
Night standard room
temperature
16 °C
System/Heating circuits/
Room1/Day room tempera-
ture
Heating circuit 1 Set
day temperature
Heating circuit 2 Set
day temperature
Heating circuit 3 Set
day temperature
20 °C
System/Heating circuits/
Room1/Night room temper-
ature
Heating circuit 1 Set
night temperature
Heating circuit 2 Set
night temperature
Heating circuit 3 Set
night temperature
16 °C
System/Heating circuits/
Heating circuit1/Curve/
Factor set room curve/heat-
ing curve change (requires
service password)
Heating circuit 1
Factor set room/flow
temp.
Heating circuit 2
Factor set room/flow
temp.
Heating circuit 3
Factor set room/flow
temp.
Factor 2
System/Heating circuits/
Room1/Room temperature
cooling
Circuit 1 Set cooling
temperature
Circuit 2 Set cooling
temperature
Circuit 3 Set cooling
temperature
20 °C
System/Heating circuits/
Heating circuit1/Curve/
Cooling curve standard
room temperature (requires
service password)
Circuit 1 Cooling
standard room tem-
perature
Circuit 2 Cooling
standard room tem-
perature
Circuit 3 Cooling
standard room tem-
perature
20 °C
System/Heating circuits/
Heating circuit1/Curve/
Cooling curve Factor set
room curve/heating curve
change (requires service
password)
Circuit 1 Cooling fac-
tor room/flow tem-
perature
Circuit 2 Cooling fac-
tor room/flow tem-
perature
Circuit 3 Cooling fac-
tor room/flow tem-
perature
Factor 2
System/Cold water/Set val-
ue/Setpoint constant
Fixed set tempera-
ture, coolant buffer
cylinder
8 °C
System/Heating circuits/
Pump circuit 1/Cooling limit
(requires service password)
Cooling limit temper-
ature circuit 1
Cooling limit temper-
ature circuit 2
Cooling limit temper-
ature circuit 3
24 °C
Commissioning/service reports
Commissioning reports
(cont.)
5549 991 GB
Service