Details of the available options
■
One heat pump is the "master", the other is the
"slave"
■
The master heat pump may be equipped with a
changeover valve for DHW heating
■
During DHW heating, the slave heat pump can
charge the heating water buffer cylinder; alternatively
both can charge this cylinder simultaneously
■
Like the master heat pump, the slave heat pump can
serve up to 3 heating circuits. Consequently a cas-
cade facilitates up to 6 heating circuits
■
Select
å
■
Select
"Login"
■
Enter the password and select
"Configuration"
■
Select
"Configuration Plant"
■
Select
"Selection external control"
Configuration
Selection external control
10:12:17
External control
Cascade slave
Fig.50
■
In system configuration, select
"Cascade slave"
under
"Selection external control"
for the slave
heat pump
■
Optional heating circuits can be selected afterwards
■
No special settings are required in the system config-
uration for the master heat pump
■
Select
å
■
Select
"Login"
■
Enter the password and select
"Configuration"
■
Select
"Parameters of sys.controller"
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5549 991 GB