93
Type WW
Single stage
Two-stage
301.BS
302.BS
125
155
125
155
200
250
300
Electrical values, control
unit
Rated voltage
1/N/PE 230 V/50 Hz
MCB/fuse protection
1 x B16A
MCB/fuse
6.3 AH (slow)/250 V~
Rated output
W
1000
1000
1000
1000
1000
1000
1000
Max. power consumption,
stage 1
W
25
25
25
25
25
25
25
Max. power consumption,
stage 2
W
20
20
20
20
20
Max. power consumption,
stages 1 & 2
W
45
45
45
45
45
Safety category/IP rating
IP20
IP20
IP20
IP20
IP20
IP20
IP20
Refrigerant circuit
Refrigerant
R410A
Refrigerant charge
kg
18.4
21.4
18.9
21.2
25.8
28.3
31.8
Permiss. operating pressure,
low pressure side
bar
18
18
18
18
18
18
18
Permiss. operating pressure,
high pressure side
bar
43
43
43
43
43
43
43
No. of hermetically sealed
scroll compressors
Type
1
1
2
2
2
2
2
Permiss. operating pres-
sure
Primary circuit
bar
6
6
6
6
6
6
6
Secondary circuit
bar
6
6
6
6
6
6
6
Dimensions
Total length
mm
1932
1932
1932
1932
2521
2521
2521
Total width
mm
911
911
911
911
911
911
911
Total height without program-
ming unit
mm
1650
1650
1650
1650
1650
1650
1650
Connections
Primary circuit flow and return
7
3"
3"
3"
3"
3"
3"
3"
Heating water flow and return
7
2
½
"
2
½
"
2
½
"
2
½
"
2
½
"
2
½
"
2
½
"
Weight
kg
1015
1055
1035
1060
1330
1380
1425
Sound power level
(tested
with reference to EN 12102/
EN ISO1914-2) Weighted total
sound power level at
W10
±
3 K
/W35
±
5 K
At rated heating output
dB(A)
61.5
63
58
60
63
64
65
Specification
Specification, type WW 301.BS125 to WW 302.BS300
(cont.)
5549 991 GB
Service
Summary of Contents for 301.BS090
Page 99: ...99 5549 991 GB...