51
"Parameters Plant"
, for further details, see page 69
■
Here you can adjust selected parameters that cannot
be adjusted in
"Configuration Plant"
■
The way the outside temperature is captured can be
adjusted here (offset and time over which the tem-
perature is averaged)
■
Here you can set the times when the compressor
can be blocked
Note
Parameters are preset. Making incorrect adjust-
ments can result in undesirable system behaviour
or system faults.
"Parameters of sys.controller"
, for further details,
see page 61
■
Parameters that only affect the controller can be set
here.
■
This includes external control
1.2. Selecting the system configuration (commis-
sioning)
■
Select
å
■
Select
"Login"
■
Enter the password and select
"Configuration"
■
Select
"Configuration Plant"
and then
"Series
selection"
Series selection
Selection series
15:17:02
Main menu
BW30x / BW35x
BW35x / Screw
Reset configuration
Fig.33
Note
Certain buttons may not appear subject to the soft-
ware version.
Note
During the first configuration after a software
update or during commissioning, initially select
"Reset configuration".
■
Select the corresponding heat pump series at
"BW30x/BW35x"
■
A description of the model size appears if a heat
pump series has already been selected
■
Continue with
Ó
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5549 991 GB