31
400 V~/230 V~ components
External connections
Terminals
Function
Explanation
12X0
Compressor 1 operating message
Floating N/O contact:
■
Closed: Compressor 1 running
■
Open: Compressor 1 not running
Connection values
■
Max. voltage: 250 V~
■
Max. switching current: 4 A (AC1)
12X2
Compressor 2 operating message
Floating N/O contact:
■
Closed: Compressor 2 running
■
Open: Compressor 2 not running
Connection values
■
Max. voltage: 250 V~
■
Max. switching current: 4 A (AC1)
12K8/11;14
Heat pump central fault message
Floating N/O contact:
■
Closed: No fault
■
Open: Heat pump fault
Connection values
■
Max. voltage: 250 V~
■
Max. switching current: 4 A (AC1)
Circuit protection from load MCB/fuse 5FC1 (observe the maximum total current of 16 A)
Terminals
Function
Explanation
13X0
Circulation pump, evaporator
Heat pump
Connection values
■
Max. output: 4000 W
■
Voltage:
400 V~/230 V~
■
Max. switching current: 9 A (AC3)
13X5
Circulation pump, condenser
Heat pump
Connection values
■
Max. output: 4000 W
■
Voltage:
400 V~/230 V~
■
Max. switching current: 9 A (AC3)
Terminals
Function
Explanation
21X1
Circulation pump, groundwater
Heat yield
Connection values
■
Max. output: 4000 W
■
Voltage:
400 V~/230 V~
■
Max. switching current: 9 A (AC3)
Note
Fit the service switch upstream of the circulation
pump.
13X2
Pressure switch, primary circuit/frost
stat
Heat yield
Insert jumper if no safety components are instal-
led.
Installation sequence
Overview of electrical connections
(cont.)
5549 991 GB
Installation