35
Terminals
Function
Explanation
21X5
Groundwater/cold water flow switch
Requires floating contact:
■
Closed:
Heat pump in operation
■
Open:
Heat pump shut down
No
jumper should be installed if a flow switch is con-
nected.
38X4
External fault message, dry cooler
Requires floating contact:
■
Closed:
Dry cooler fault
■
Open:
Dry cooler OK
19X0
Optional heat pump emergency stop
switch
Requires floating contact:
■
Closed:
Heat pump in operation
■
Open:
Heat pump shut down
No
jumper should be installed if a flow switch is con-
nected.
19X2
Power supply utility control
Economy tariff peak block
19X4
External demand 1
Requires floating contact:
■
Closed:
Demand 1 active
No
jumper should be installed if a start command is
connected.
19X6
External demand 2
Requires floating contact:
■
Closed:
Demand 2 active
No
jumper should be installed if a start command is
connected.
19x8
External changeover command
Heating/cooling
Requires floating contact:
■
Closed: Cooling
■
Open: Heating
External demand 1+2
Terminal 19x4,
1+2
Terminal 19x6,
1+2
Description
Open
Open
Not enabled
Closed
Open
Enable 1 stage
Open
Closed
Enable 2 stages
Closed
Closed
Enable 3 stages
Note
With the contact closed, 24 VDC must be available
at terminal number 2.
Note
The terminal strip for internal heat pump components
is position
6
in the graphic on page 30.
Installation sequence
Overview of electrical connections
(cont.)
5549 991 GB
Installation