Correct setting of parameter "Factor set room
curve/heating curve change"
This factor determines the relationship between the
room temperature adjustment and the necessary modi-
fication of the flow temperature.
Theory:
This factor is required as the room tempera-
ture is always below the flow temperature.
Optimal factor adjustment: Determine the value by
which the flow temperature needs to be increased in
order to achieve a 1 °C rise in room temperature. For a
description of capturing the outside temperature, see
page 71.
Cooling circuits
The cooling curve results from: outside temperature
and set cooling temperature. This means only one off-
set and one slope can be adjusted.
Cooling circuits are regulated and adjusted in the
same way as heating circuits (
Please note
: observe
the difference described above).
■
Select menu
å
■
Select
"System"
■
Select
"Heating circuits"
■
Select
"Room 1"
Heating circuit adjustments for the user
13:18:56
17/04/2013
Plant
05:00
05:00
05:00
05:00
05:00
05:00
05:00
22:00
22:00
22:00
22:00
22:00
22:00
22:00
-
h
-
h
-
h
-
h
-
h
-
h
-
h
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
Sunday
Clock: Day - operation
Back
Room 1
Login
20.0 °C
16.0 °C
Day:
Night:
Room temperature
Holiday program
Holiday operation
Number of days
5
Outstanding days
0
Fig.59
Instructing the system user
The system installer should hand the operating instruc-
tions to the system user and instruct the user in oper-
ating the system.
This includes all components installed as accessories,
e.g. remote control units. In addition, the system instal-
ler must make the user aware of the required mainte-
nance work.
Please refer to the "Vitotronic SPS operating
instructions" for further details of the operation.
Commissioning, inspection, maintenance
Commissioning the system
(cont.)
5549 991 GB