89
Operation: Brine/water
Type BW
Single stage
Two-stage
301.BS
302.BS
090
120
090
120
150
180
250
Output data
to EN 14511 (B0/W35,
5 K spread)
Rated heating output
kW
93
121
89.4
117.2
150
182
240
Cooling capacity
kW
74.5
96.4
72
93.8
120.1
145.4
191.4
Power consumption
kW
19.5
24.8
18.3
24.4
31.9
39.6
50.4
Coefficient of performance
ε
(COP)
4.77
4.83
4.88
4.8
4.70
4.60
4.76
Brine
(primary circuit)
Capacity
l
33.0
42.0
33.0
42.0
55.2
69.0
89.4
Nominal flow rate to
EN 14511
m
³
/h
24.5
31.7
24.0
31.3
39.5
47.8
62.9
Minimum flow rate (5 K
spread)
m
³
/h
15.0
19.0
14.5
18.8
24.0
30.0
39.0
Pressure drop
mbar
120
120
120
120
130
140
180
Max. flow temperature
°C
20
20
20
20
20
20
20
Min. flow temperature
°C
-5
-5
-5
-5
-5
-5
-5
Heating water
(secondary
circuit)
Capacity
l
22.7
28.7
22.7
28.7
38.7
53.5
57.1
Nominal flow rate to
EN 14511
m
³
/h
16.0
21.0
15.4
20.3
25.8
31.4
41.4
Minimum flow rate (10 K
spread)
m
³
/h
8.0
10.5
7.8
10.2
12.9
15.7
20.7
Pressure drop (at minimum
flow rate)
mbar
100
100
100
100
100
100
120
Flow temperature at min. pri-
mary circuit flow temperature
0 °C
°C
55
55
60
60
55
55
55
Flow temperature at min. pri-
mary circuit flow temperature
+5 °C
°C
60
60
65
65
60
60
60
Operation: Water/water with intermediate circuit
Type BW
Single stage
Two-stage
301.BS
302.BS
090
120
090
120
150
180
250
Output data
to EN 14511 (W10/W35,
5 K spread)
Rated heating output
kW
125
152
118.8
153.0
198
235
302
Cooling capacity
kW
104.5
128
101
129.0
168
197
252
Power consumption
kW
21
25.6
18.9
25.3
32.1
41
51.8
Coefficient of performance
ε
(COP)
5.95
5.93
6.2
6.05
6.10
5.73
5.83
Specification
Specification, type BW 301.BS090 to BW 302.BS250
5549 991 GB
Service
Summary of Contents for 301.BS090
Page 99: ...99 5549 991 GB...