NOTE: DIP switches labeled ON or CLOSED and OFF or OPEN have the same meaning.
Figure 23
DIP Switch Label
Competitive Protocol Settings, SW2 Switches 5-8
Pelco:
Switch 5 is ON, switches 6-8 are OFF
Sensormatic:
Switch 6 is ON, switches 5, 7, 8 are OFF
Ultrak:
Switches 5 and 6 are ON, switches 7-8 are OFF
Philips:
Switch 7 is ON, switches 5, 6, 8 are OFF
Cohu:
Switches 5 and 7 are ON, switches 6 and 8 are OFF
Kalatel:
Switches 6 and 7 are ON, switches 5 and 8 are OFF
Panasonic:
Switches 5 and 8 are ON, switches 6 and 7 are OFF
NTCIP:
The dome is specifically coded from the factory or flash upgraded. It cannot
be switched to other protocols without first flashing the firmware back to standard
factory protocol. Switches 5-8 are not used and switch 3 must be OFF for Duplex.
LAN (ViconNet): SW2
Switches 3 and 4 are OFF; switch 1 on
SW1
to ON
Caution: Competitive protocols are not available in LAN (ViconNet) mode.
Note: For Pelco Keypad with 2400 baud, switch 3 on SW2 must be set to ON; Pelco is D protocol.
40
•
6BConfiguration
XX134-07-00 Rev 908 SurveyorVFT Camera Dome System