44
Boiler primary pump slowing-down
[min.]
P 52
We select boiler pump slowing-down on this line.
Boiler primary pump switch-on temperature
[
o
C]
P 53
Once this set boiler temperature has been achieved the boiler primary pump will
switch on. The pump will switch off once the temperature has dropped by 5 °C
below the temperature set for pump switching-on.
Day of boiler primary pump spinning
P 54
On the determined day the pump spinning will be done at 12:00 h for 30 sec.
Value 1 - 7 – corresponds to days from Monday to Sunday
Value 0 –primary pump spinning is not active
Value 8 – primary pump spinning is active every day
Note: If at this time the pump is working the function is not active
Heating circuit pump man/auto
P 55
Setting of pump control type. Man – pump manual run, Auto – pump automatic run
according to current requirements.
Value 0 – Man
Value 1 – Auto
Heating circuit pump off/on
P 56
Circuit pump switched on in case we have selected value 0 – Man on the line no.
55.
Value 0 – Switched off
Value 1 – Switched on
Note: In case value 0 is selected in parameter P 55 it is necessary to select here
the value 1. If it be to the contrary the pump will not be active.
Heating circuit pump slowing-down
[min.]
P 57
We select heating circuit pump slowing-down on this line.
Day of heating circuit pump spinning
P 58
On the determined day the pump spinning will be done at 12:00 h for 30 sec.
Value 1 - 7 – corresponds to days from Monday to Sunday
Value 0 –pump spinning is not active
Value 8 –pump spinning is active every day
Note: If at this time the pump is working the function is not active
Warm water pump man/auto
P 59
Setting of type of pump control; Man –pump manual run, Auto – pump automatic
run according to the current requirements.
Value 0 – Man
Value 1 – Auto
Attention! The value 0 is only designed for HW pump service testing.
The permanent setting of pump manual run can result in water heater chilling.
Therefore keep the set value1.
Warm water pump off/on
P 60
Warm water pump switched on in case we have selected value 0 – Man on the
line no. 59.
Value 0 – Switched off
Value 1 – Switched on
Note: In case the value 0 is selected in P 59 parameter it is necessary to select
here the value 1. If it be to the contrary the pump will not be active.
Warm water pump slowing-down
[min.]
P 61
We select warm water pump slowing-down on this line