Parameter
Description
Units
Set by the
manufacturer
Range
Resolution
P 200
Ventilator X1 hard coal
[%]
0
0
0
P 201
Ventilator Y1 hard coal
[%]
28
23 … 33
1
P 202
Ventilator X2 hard coal
[%]
33
33
0
P 203
Ventilator Y2 hard coal
[%]
34
29 … 39
1
P 204
Ventilator X3 hard coal
[%]
66
66
0
P 205
Ventilator Y3 hard coal
[%]
70
65 … 75
1
P 206
Ventilator X4 hard coal
[%]
100
100
0
P 207
Ventilator Y4 hard coal
[%]
75
70 … 80
1
P 208
Ventilator slowing-down in the attenuation
regime– hard coal
[s]
30
5 … 120
1
P 209
Ventilator output in the attenuation – hard
coal
[%]
100
50 … 100
1
P 210
Feeder X1 pellets
[%]
0
0
0
P 211
Feeder Y1 pellets
[s]
60
50 … 70
1
P 212
Feeder X2 pellets
[%]
33
33
0
P 213
Feeder Y2 pellets
[s]
29
19 … 39
1
P 214
Feeder X3 pellets
[%]
66
66
0
P 215
Feeder Y3 pellets
[s]
16
11 … 21
1
P 216
Feeder X4 pellets
[%]
100
100
0
P 217
Feeder Y4 pellets
[s]
10
5 … 15
1
P 218
Feeder runtime in the attenuation – pellets
[s]
15
13 … 20
1
P 219
Standstill time(delay) feeder in the
attenuation – pellets
[min.]
10
5 … 15
1
P 220
Ventilator X1 pellets
[%]
0
0
0
P 221
Ventilator Y1 pellets
[%]
8
6 … 13
1
P 222
Ventilator X2 pellets
[%]
33
33
0
P 223
Ventilator Y2 pellets
[%]
16
11 … 21
1
P 224
Ventilator X3 pellets
[%]
66
66
0
P 225
Ventilator Y3 pellets
[%]
36
31 … 41
1
P 226
Ventilator X4 pellets
[%]
100
100
0
P 227
Ventilator Y4 pellets
[%]
46
41 … 51
1
P 228
Ventilator slowing-down in the attenuation
regime– pellets
[s]
3
1 … 60
1
P 229
Ventilator output in the attenuation – pellets
[%]
100
50 … 100
1
P 232
Outside sensor deactivation
0
0 … 1
1
P 233
Diagnostics HC
-
-
-
P 234
Diagnostics boiler
-
-
-
P 235
Restoration of manufacturer’s setting
0
0 … 1
1
P 238
Year
-
2000 - 2050
1
P 239
Date
-
01.01. – 31. 12.
Day
P 240
Time
-
00:00 – 23:59
Minute
Tab. no. 8 Parameters – Pump heating circuit
Parameter
Description
Units
Set by the
manufacturer
Range
Resolution
P 1
Current outside temperature
[
o
C]
-
-20 … 50
0,1
P 2
Current boiler temperature
[
o
C]
-
5 … 100
0,1
P 4
Desired heating circuit temperature
[
o
C]
-
0 … 80
0,1
P 5
Current temperature HW
[
o
C]
-
5 … 100
0,1
P 6
Desired boiler temperature in case of HW
heating
[
o
C]
-
0 … 75
1
P 8
Current feeder temperature
[
o
C]
-
5 … 100
0,1
P 9
Current space temperature
[
o
C]
-
0 … 40
0,1
P 11
Desired boiler temperature
[
o
C]
-
20 … 85
0,1
P 12
Current ventilator output
[%]
-
0 … 100
0,1
P 15
Faults
-
0 … 15
P 19
Parallel shift in the heating curve
[
o
C]
0
-10 … 10
1
P 20
Fuel type
1
1 … 4
1
P 21
Slope of heating curve
1,5
0,1 … 4
0,1