QAA 88 device – boiler unit
•
Outside sensor QAC34/101
•
Thermostatic valve (Filling valve) - series VTC312
(external thread) from ESBE (minimum return water
temperature 45
o
C) (ord. code: 5100 15 00)
•
Three-way mixing valve VBI31.20 with drive
SQK34.00
•
Heating branch sensor QAD36/101
•
Water heater thermostat type: 7K1.6R326.00A (only
in case boiler is used for HW heating)
Equithermal control without space effect
•
QAA 88 device – space unit
•
Outside sensor QAC34/101 – is not used
•
Thermostatic valve (Filling valve) - series VTC312
(external thread) from ESBE (minimum return water
temperature 45
o
C) (ord. code: 5100 15 00)
•
Three-way mixing valve VBI31.20 with drive
SQK34.00
•
Heating branch sensor QAD36/101
•
Water heater thermostat type: 7K1.6R326.00A (only
in case boiler is used for HW heating.)
Space control
•
QAA 88 device – space unit
•
HMI service unit for Saphir regulator operation
(ACX84.910/ALG) – only by request
•
Outside sensorQAC34/101
•
Thermostatic valve (Filling valve) - series VTC312
(external thread) from ESBE (minimum return water
temperature 45
o
C) (ord. code: 5100 15 00)
•
Three-way mixing valve VBI31.20 with drive
SQK34.00
•
Heating branch sensor QAD36/101
•
Water heater thermostat type: 7K1.6R326.00A (only
in case boiler is used for HW heating)
Equithermal control with space effect
•
QAA 88 device – space unit
•
HMI Service unit for Saphir regulator operation
(ACX84.910/ALG) – only by request
•
Outside sensorQAC34/101 – is not used
•
Thermostatic valve (Filling valve) - series VTC312
(external thread) from ESBE (minimum return water
temperaturem45
o
C) (ord. code: 5100 15 00)
•
Three-way mixing valve VBI31.20 with drive
SQK34.00
•
Heating branch sensor QAD36/101
•
Water heater thermostat type: 7K1.6R326.00A (only
in case boiler is used for HW heating)
Space control
•
HMI Service unit for Saphir regulator operation
(ACX84.910/ALG) – only by request
•
Outside sensorQAC34/101
•
Thermostatic valve (Filling valve) - series VTC312
(external thread) from ESBE (minimum return water
temperature 45
o
C) (ord. code: 5100 15 00)
•
Three-way mixing valve VBI31.20 with drive
SQK34.00
•
Heating branch sensor QAD36/101
•
Water heater thermostat type: 7K1.6R326.00A (only
in case boiler is used for HW heating)
Equithermal control without space effect
Note:
In case the equithermal control is without space effect we must suitably set P 21 parameter. If there is not
reached the desired P 103 (P 106 and P 109) space temperature we must increase the slope of heating
curve. Correct setting of heating curve slope is done by the end user. The changes do not become evidayt
immediately, but with regard to the equipment adaptability and various buildings inertia they become evidayt
after some time which might make several days.