Example
Continuing the preceding data center example (in
Calculate the Heat Load to be Handled by Liebert XD
on page 21) of a server room 2000 ft2 with 30 racks (15 producing 20kW of heat per rack and 15
producing 10 kW of heat per rack), the three Liebert XDPs required can supply coolant to various types of
Liebert XD modules. For instance, the racks with 20kW per rack could be cooled with either Liebert
XDH20, Liebert XDO20 or Liebert XDR20. The racks with 10kW per rack could be cooled using the Liebert
XDV10.
1. For the 15 racks with 20kW of heat each, the total load is:
15 racks x 20kW per rack = 300kW
The perimeter cooling will address the first 2-5kW per rack:
2kW x 15 racks = 30kW
The Liebert XD solution would have to remove 270kW for these racks with higher heat load.
300kW - 30kW = 270kW
Module
Conditions °F (°C)
Capacity at Conditions, kW
Load, kW
Modules Required
Liebert XDH20
98 (36.6)
22.0
270
13
Liebert XDO20
98 (36.6)
22.5
270
12
Liebert XDR20
98 (36.6)
22.0
270
15
2. For the 15 racks with 10kW of heat each, the total load is:
15 racks x 10kW per rack = 150kW
The base cooling will address the first 2-5kW/rack:
2kW x 15 racks = 30kW
The Liebert XD solution would have to remove 120kW for these racks with a higher heat load.
150kW - 30kW = 120kW
Module
Conditions °F (°C)
Capacity at Conditions, kW
Load,
kW
Modules Required
Liebert XDV10
98 (36.6)
10.0
120
12
3. For this data center example, the Liebert XD solution would consist of:
•
3 Liebert XDP160s
•
12 Liebert XDV10s
and any of the following:
•
13 Liebert XDH20s
•
12 Liebert XDO20s
•
15 Liebert XDR20s
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
23
Summary of Contents for Liebert XD Series
Page 1: ...Liebert Xtreme Density System Design Manual...
Page 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Page 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Page 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Page 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Page 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Page 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Page 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Page 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Page 199: ......