Outdoor
Ambient
°F (°C)
Model
50/60Hz
Number
of Fans
Connection Size, OD,
In.
Net
Weight
lb (kg)
Receiver Part
#
Receivers
per
Condenser
Net
Weight
lb (kg)
Hot Gas
Liquid
-30 to 100
(-34 to 38)
DCSL415
4
1-3/8
1-1/8
840 (381)
185010G2
1
/G4
2
1
260 (118)
-30 to 105
(-34 to 41)
DCSL616
6
(2) 1-5/8
(2) 1-1/8
1380 (626)
179713G1
1
/G2
2
1
424 (192)
35 to 105
(-34 to 41)
DCSL616
6
(2) 1-5/8
(2) 1-1/8
1380 (626)
181610G2
1
/G4
2
1
200 (91)
1. 120V
2. 230V
Table 6.2 Condenser weights and connections
Model #
083, 104, 28K
165, 205, 60K
251, 308, 90K
415, 510
616
830, 1010
# of Fans
1
2
3
4
6
8
Input
Volta
ge
p
h
F
L
A
W
SA
O
P
D
F
L
A
W
SA
O
P
D
F
L
A
W
SA
O
P
D
F
L
A
W
SA
O
P
D
F
L
A
W
SA
O
P
D
F
L
A
W
SA
O
P
D
208/23
0
3
3.5
4.4
15
7.0
7.9
15
10.5
11.4
15
14.0
14.9
20
21.0
21.9
25
28.0
28.9
35
460
1.7
2.1
15
3.4
3.8
15
5.1
5.5
15
6.8
7.2
15
10.2
10.6
15
13.6
14.0
20
575
1.4
1.8
15
2.8
3.2
15
4.2
4.6
15
5.6
6.0
15
8.4
8.8
15
11.2
11.6
15
FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device
Table 6.3 60Hz electrical condenser data—Liebert Lee-Temp controlled/fan-cycling
Condenser Control Type
Liebert Lee Temp Controlled/Fan-Cycling
Model #
# of Fans
Input Voltage - Phase
200/230-3
380/415-3
415
4
14.0
6.8
616
6
21.0
10.2
Table 6.4 50 Hz condenser full load amp values
Rated Voltage - Single Phase
120
200/208/230
Watts/Receiver
150
300
450
150
300
450
Full Load Amps
1.4
2.8
4.2
0.7
1.4
2.1
Wire Size Amps
1.8
3.5
5.3
0.9
1.8
2.7
Maximum Overcurrent
Protection Device, Amps
15
15
15
15
15
15
The Liebert Lee-Temp receiver requires a separate power feed for heaters. The condenser is not designed to supply power to the receiver.
Table 6.5 Liebert Lee-Temp receiver electrical data, 50Hz and 60Hz
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
122
Summary of Contents for Liebert XD Series
Page 1: ...Liebert Xtreme Density System Design Manual...
Page 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Page 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Page 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Page 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Page 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Page 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Page 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Page 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Page 199: ......