XDC160 Glycol Floor Stand - 60Hz - 40% EG
189192G3
Outside Ambient °F (°C)
95 (35)
100 (38)
105 (41)
Max Entering Fluid Temp °F (°C)
110 (43)
110 (43)
110 (43)
Performance Data
Cooling capacity, tons (kW)
42.5 (149.4)
Total Heat Rejection, (kW)
192.6
Flow, GPM
204
Pressure Drop, psi (ft water)
35.9 (82.9)
Heat Rejection Equipment
Drycooler
DDNT 940A
2 x DDNT 880A*
Drycooler Pressure Drop, psi (ft water)
6.5 (15.1)
2.7 (6.3)
Glycol pump package - 10HP
460V - D10ANTS1317; 208V - D10YNTS1317
Pump Control Package - 208V
RP020HY04S0758
Pump Control Package - 460V
RP020HA08S0758
Pump Total Head @ 204 GPM, ft water
145
Water regulating valve size
1-1/4"
Piping Connections
Water / glycol supply and return lines
2-5/8"
*When multiple drycoolers are used ensure flow is balanced.
Table 9.16 Floor stand specifications—Liebert XDC with 40% ethylene glycol
Figure 9.6 Liebert XDC model number nomenclature
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
196
Summary of Contents for Liebert XD Series
Page 1: ...Liebert Xtreme Density System Design Manual...
Page 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Page 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Page 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Page 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Page 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Page 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Page 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Page 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Page 199: ......