Liebert XDC 160
Equivalent
Length, ft., (m)
*Hot Gas Line, in.
Liquid Line, in.
50 (15)
1-1/8
7/8
100 (30)
1-1/8
1-1/8
150 (45)
1-3/8
1-1/8
200 (60)
1-3/8
1-1/8
* Double risers are required when hot gas vertical rise is 15ft. (4.6m) or more.
Source: DPN000937, Pg. 3, Rev. 11
Table 6.7 Recommended refrigerant line sizes, DX R-407C, OD copper
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
130