Models
XDP160RC--3
XDP160RA--3
XDP160RM--3
Cooling Capacity, Nominal
160kW / 46 Tons, 60Hz
140kW / 40 Tons, 50Hz
Each capacity is based on 45ºF (7ºC) entering water temperature and 140gpm (530lpm) water flow rate.
Capacity is reduced when glycol mixtures are used in place of 100% water.
Minimum Load
30% of nominal system capacity or 48kW (163,800BTU/H)
Electrical Requirements
Input
208V/3ph/60Hz
460V/3/ph60Hz
380/415V/3ph/50Hz
Full Load Amps
2.1A
2.3A
Dimensions, inches (mm)
Height – Unit only
78 (1981)
Height – As shipped
83 (2108)
Width
38 (965)
Depth
34 (864)
Weight, lb (kg)
Unit only
821 (372)
Shipping weight
Domestic: 990 (449); Export: 1067 (484)
Installed, with refrigerant and chilled
water
1038 (471)
Pipe Connections
Refrigerant supply to Liebert XD
cooling module
1-1/8" OD, Cu
Refrigerant return from Liebert XD
cooling module
2-1/8" OD, Cu
Chilled water supply and return
2-5/8" OD, Cu
Control valve
2-way, 2" nominal; 35 PSIG close-off pressure rating;
150 PSIG maximum allowable pressure
Pressure Drop – Chilled Water Side
20 psig (137kPa, 1.38bar), with 140 gpm (530lpm) water flow rate,
control valve fully open
Temperature Rise – Chilled Water
Side at rated flow, °F (°C)
8.0 (4.4)
6.9 (3.8)
Number of Liebert XD Cooling Modules Connected, Maximum (Minimum)
Liebert XDCF10
16 (5)
Liebert XDH20
8 (3)
Liebert XDH32
5 (2)
Liebert XDV8
20 (6)
Liebert XDV10
16 (5)
Liebert XDO16
10 (3)
Liebert XDO20
8 (3)
Cabinet Exterior Finish
Black, matte finish, heat-fused powder coat
Operating Ambient
Temperature, Maximum, °F (°C)
86 (30)
Agency
Approvals
CSA 60Hz
CE 50Hz
Table 9.17 Liebert XDP160 specifications
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
197
Summary of Contents for Liebert XD Series
Page 1: ...Liebert Xtreme Density System Design Manual...
Page 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Page 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Page 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Page 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Page 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Page 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Page 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Page 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Page 199: ......