Figure 3.21 Hard-pipe connection diagram for Liebert cooling modules
3.18 Piping Details—Return Header Port Orientation
The return header port from a Liebert XD cooling module is a gravity return and must be properly
oriented to the refrigerant return header for proper flow. The return header contains R134a refrigerant in
gas and liquid form. Improperly connecting a cooling module’s return header port to the return header
could permit liquid refrigerant to back up into the cooling module. See Figure 3.22 on the facing page for
proper orientation.
Supply header ports can be oriented at any angle to the header because supply headers carry only liquid
R134a refrigerant and are not gravity operated.
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
44
Summary of Contents for Liebert XD Series
Page 1: ...Liebert Xtreme Density System Design Manual...
Page 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Page 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Page 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Page 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Page 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Page 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Page 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Page 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Page 199: ......