PROPERTY
DESCRIPTION
DEFAULT
VALUE
Enabled
Enable or Disable
Enabled
Name
Name of the sensor
Sensor ID
Type
Smoke, Door, Leak or Motion. Sensor type
can only be selected when the sensor is
added.
Smoke
Default
State
Open or Closed
Open
Location
The sensor's location or position
Blank
To add, enable or remove a COM digital input sensor:
1.
Click
Administration - Sensors - COM Digital Input.
2.
Enter the name of the sensor.
3.
Select the port (DI1 or DI2).
4. Select the type of sensor and click
Add
.
5.
Click the sensor name, choose the normal status and click
Enable
.
6. To remove the sensor, click the sensor name and click
Remove
.
5.12.2 Digital inputs
The digital inputs collect smoke, leak and motion data. They can be connected to the DI1/DI2 ports on the back of the
appliance.
PROPERTY
DESCRIPTION
DEFAULT VALUE
Sensor #
Sensor ID (Read Only)
System Defined
Value
Enabled
Enable or Disable
Enabled
Name
Name of the sensor
Sensor ID
Default
State
Closed or Open
Open
Location
The sensor's location or position
Blank
Type
Type of sensor: Custom, smoke, leak
or motion
Custom
Address
The serial number of the sensor (Read
Only)
Information from
Sensor
Table 5.17 Digital Input Properties
To detect, enable/disable or edit a OneWire digital input sensor:
1.
Click
Administration - Sensors - Digital Input
.
2.
Click
Detect
to search for new sensors.
3.
Click the sensor number, choose the type of sensor or update the normal status.
4. Click
Enable
to enable or disable the sensor.
5.12.3 Environment
Environment sensors collect temperature and humidity data. They can be connected to the TH1/TH2 ports on the back of
the appliance.