Calibration
LFXG-H Installation and Operation Guide
55
Procedure 3.6: To collect linearizer table data
4 Calculating the linearity
After collecting the data for a linearizer table, the transmitter uses the data
to calculate a new calibration linearizer table. The
Calc linearity
function
initiates this calculation.
You must perform this step before the Calculate Calibration step (see the
next section).
Before calculating the linearizer:
1.
Select non-linear table for the linearizer curve.
2.
Collect linearizer data.
1.
Select
Calibration | Linearizer Data Pt | Create Data Point
.
2.
At the prompt, enter the actual known level of process.
3.
Accept or reject the results when they appear.
4.
Repeat procedure for all available levels.
Note:
The simple method skips this step.
Note: Include the data for the Cal Low and Cal High with
the linearizer data before you perform Calculate
linearity. If you did not perform a linearizer data
collection while the process was at the levels for
Cal Low and Cal High, you can manually add those
values to the linearizer data.
To add a data point to the linearizer data, you must
know the level in engineering units and the sensor
counts.
Summary of Contents for FiberFlex LFXG-H
Page 2: ......
Page 4: ...ii LFXG H Installation and Operation Guide NOTES...
Page 6: ...iv LFXG H Installation and Operation Guide...
Page 14: ...Preface xii LFXG H Installation and Operation Guide...
Page 34: ...Installation 32 LFXG H Installation and Operation Guide FiberFlex mounting...
Page 91: ...Diagnostics and repair LFXG H Installation and Operation Guide 89 Source Functions...
Page 100: ...98 LSGH Installation and Operation Guide NOTES...
Page 101: ......