Calibration
46
LFXG-H Installation and Operation Guide
The internal software calculates a linearizer curve based on data points.
The curve is the most accurate between the Cal Low Level and Cal High
Level.
So, it is best to take the Cal Low and Cal High samples as close as possible
to the Min Level and Max Level to maximize the accuracy within the span.
Cal Low Counts
Cal High Counts
Min Level
Cal Low Level
Cal High Level
Max Level
Actual Level (engineering units)
Standard
Simple
Raw counts vs. actual count level with linearizers
Raw Sensor Counts