Installation, Operating & Maintenance Instructions
Series 612 DN 250 (I.D. 10”), EtherCAT
VAT Vakuumventile AG, CH-9469 Haag, Switzerland
Tel +41 81 771 61 61 Fax +41 81 771 48 30 [email protected] www.vatvalve.com
282408EB
2012-04-23
40/81
3.6.3 Valve and sensor configuration
Basic valve configuration must be adapted according to application needs.
Definition of valve plate position in case of:
o
After power up
, default is ‘close‘.
o
Power failure
, default is ‘not defined‘. Only for versions that have Power Fail Option equipped [612 . . - . .
C
. - . . .
. or 612 . . - . .
H
. - . . . . ].
o
Network failure
, default setting refer to individual product data sheet.
ZERO function. This may be ‘disabled’ or ‘enabled’. Default is ‘enabled‘. Refer also to «ZERO».
Local operation
:
(‘Control View’ or ‘Control Performance Analyzer’)
Remote operation
:
1. Do power up configuration in menu
‘Setup / Valve’.
2. Do power fail configuration in menu
‘Setup / Valve’.
3. Do network failure configuration
Go to ‘Tools / Terminal’ menu and use the following
commands
to change the configuration: s:04abcdefgh[CR]
to read the configuration:
i:04[CR]
Note:
Each element is separated with square
brackets for clarity. Square brackets are not part of
command syntax. All elements are ASCII characters.
There are no spaces between the elements
necessary. Command is case sensitive.
abcd
reserved; do not change
e
0
= valve will close
1
= valve will open
2
= valve no change
fgh
reserved; do not change
Note:
It’s not possible to do ‘Valve and sensor
configuration‘ via EtherCAT.
4. Enable or disable ZERO function in menu
‘Setup / Sensor’.
5.
Do sensor configuration in menu ‘Setup / Sensor’.
Note:
Read first current configuration and do not change reserved bits when sending new configuration.