On the display
Explanation
Summer mode
(Heating curve)
The summer mode specifies the outdoor temperature at which
the boiler stops heating and activates the ECO function.
Selectable values range from 0 to 40°C. The factory setting is
17°C.
Language selection
(Main menu)
Selectable languages are Swedish, Norwegian and English.
On the display
Explanation
Temp guard level
(Installation engineer
settings/ Advanced)
Temperature at which the over-temperature protection
is activated. Factory setting 15.
Temp guard type
(Installation engineer
settings/ Advanced)
Choice of method for the over-temperature protection
function. Select 0 for absolute value, the value that is set
under Temp guard level. Select 1 for the relative value when
Temp guard level is added to the setpoint. Factory setting is
relative value.
Time and date
(Main menu)
Basic settings that can be reset if the boiler is disconnected
from the power supply for more than 3 to 4 days.
Allow buzzer
(Installation engineer
settings/ Advanced)
Select ON to activate the alarm signal and select OFF to
deactivate the alarm signal. The factory setting is ON.
USB
(Installation engineer
settings/ Advanced)
This function is under development.
Outdoor temperature
(Current temperatures)
The current temperature registered by the outdoor sensor.
OTC setting
(Installation engineer
settings)
Settings for the outdoor sensor.
Heating curve
(Main menu)
The heating curve controls the temperature of the boiler in
relation to the outdoor temperature. If a room unit is installed,
it adds the indoor measurement value to the boiler.
Unlock Advanced in Installation engineer settings
The code for unlocking Advanced settings is 21.
1.
Select Installation engineer settings.
2.
Select Advanced.
3.
Press the plus button until the number two appears in the black box below the
text ACCESS CODE.
4.
Move the cursor to the right.
5.
Press the plus button until the number 1 appears.
6.
Press the right arrow key TWICE. You are now logged into Installation engineer
settings/Advanced.
After 15 minutes of inactivity, the boiler will
automatically log you out of Installation
engineer settings/Advanced.