MODBUSAppendix A — MODBUS Implementation
Varec, Inc.
159
5
Bit Field
AlmStat (Tank Data > AlmStat)
Bit Usage
0 CRIT LO LEVEL
1 ADV LO LEVEL
2 ADV HI LEVEL
3 CRIT HI LEVEL
4 CRIT LO TEMP
5 ADV LO TEMP
6 ADV HI TEMP
7 CRIT HI TEMP
8 HW IN 1
9 HW IN 2
10 HW IN 3 *
11 NW IN 4 *
12 – 15 RESERVED
* when optional AC Power module is installed
6
Bit Field
DiagStat (Tank Data > DiagStat)
Bit Usage
0 BAD LEVEL
1 BAD TEMP
2 – 15 RESERVED
7
Bit Field
CmdsBit Usage
0 – 15 RESERVED
8
Integer
FDISK (Encoder Data > FDisk)
9
Integer
IDISK (Encoder Data > IDisk)
10
Scaled
Crit Low Level Setpoint (MODBUS > CritLowLevel)
11
Scaled
Adv Low Level Setpoint (MODBUS > AdvLowLevel)
12
Scaled
Adv High Level Setpoint (MODBUS > AdvHighLevel)
13
Scaled
Crit High Level Setpoint (MODBUS > CritHighLevel)
14
Scaled
Level Deadband (MODBUS > LDeadband)
15
Scaled
Crit Low Temp Setpoint (MODBUS > CritLowTemp)
16
Scaled
Adv Low Temp Setpoint (MODBUS > AdvLowTemp)
17
Scaled
Adv High Temp Setpoint (MODBUS > AdvHighTemp)
18
Scaled
Crit High Temp Setpoint (MODBUS > CritHighTemp)
19
Scaled
Temp Deadband (MODBUS > TDeadband)
Register Number
Type
Description
Summary of Contents for 2920
Page 2: ......
Page 16: ...2920 Float Tape Transmitter 1 Introduction 6 Installation and Operations Manual...
Page 114: ...2920 Float Tape Transmitter 6 Bi Phase Mark 104 Installation and Operations Manual...
Page 120: ...2920 Float Tape Transmitter 7 MODBUS 110 Installation and Operations Manual...
Page 126: ...2920 Float Tape Transmitter 9 L J TankWay 116 Installation and Operations Manual...
Page 158: ...2920 Float Tape Transmitter 14 Ordering Information 148 Installation and Operations Manual...
Page 193: ......