VAMP 130
Overcurrent and earth-fault relay
Technical Description
VAMP Ltd
38
Vamp 24h support phone : +358 (0)40 573 6316
VM130.EN003
Immunity
- Static discharge (ESD)
EN 61000-4-2, class III
6 kV contact discharge
8 kV air discharge
- Fast transients (EFT)
EN 61000-4-4, class III
2 kV, 5/50 ns, 5 kHz, +/-
- Surge
EN 61000-4-5, class III
1 kV, 1.2/50
P
s, common mode
2 kV, 1.2/50
P
s, differential mode
- Conducted RF field
EN 61000-4-6
0.15 - 80 MHz, 10 V/m, 80% AM (1 kHz)
- Emitted RF field
EN 61000-4-3
80 - 1000 MHz, 10 V/m, 80% AM (1 kHz)
- GSM test
EN 61000-4-3
900 MHz, 10 V/m, pulse modulated
1 MHz burst
IEC 60255-22-1
1 kV, differential mode
2,5 kV, common mode
Voltage interruption
IEC 60255-11
5.2.2.
Test voltages
Insulation test voltage (IEC 60255-5)
2 kV, 50 Hz, 1 min
Surge voltage (IEC 60255-5)
5 kV, 1,2/50
P
s, 0,5 J
5.2.3.
Mechanical tests
Vibration (IEC 60255-21-1)
10 - 60 Hz, amplitude ±0.035 mm
60 - 150 Hz, acceleration 0.5g
sweep rate 1 octave/min
20 periods in X-, Y- and Z axis direction
Shock (IEC 60255-21-1)
half sine, acceleration 5 g, duration 11 ms
3 shocks in X-, Y- and Z axis direction
5.2.4.
Environmental conditions
Operating temperature
-10 to +55 ×C
Transport and storage temperature
-40 to +70 ×C
Relative humidity
< 75% (1 year, average value)
< 90% (30 days per year, no condensation
permitted)
5.2.5.
Casing
Degree of protection (IEC 60529)
IP20
Dimensions (W x H x D)
99 x 155 x 225 mm
Weight
2.3 kg