VAMP Ltd
Overcurrent and earth-fault relay
Technical Description
VAMP 130
VM130.EN003
Vamp 24h support phone : +358 (0)40 573 6316
7
2.2.
Relay protection functions
2.2.1.
Overcurrent protection I>, I>>, I>>> (50/51)
The three-phase overcurrent unit comprises three separately
adjustable overcurrent stages, i.e. stage I>, I>> and I>>>.
The overcurrent unit measures the fundamental frequency
component of the phase currents.
Stage I> can be configured for definite time or inverse time
operation characteristic. Stage I>> and stage I>>> have
definite time characteristic.
Figure 2.2.1-1 shows the functional block diagram of stage I>.
&
t
³1
&
&
>
t
s
t
r
MAX
3vIslohko
Setting I>s
Delay
Definite / inverse
time
Enable events
Inverse time
characteristics
Multiplier
Start
Trip
Register
event
Register
event
Im1
Im2
Im3
Block
Figure 2.2.1-1 Block diagram of the three-phase overcurrent stage I>.
Parameters of the overcurrent stages:
I>, I>>, I>>> (50/51)
Parameter:
Value/unit:
Measured
value
ILmax
A
Max. value of phase currents
IL1, IL2, IL3 primary values
I>, I>>,
I>>>
A
Setting value in primary
current units
I>, I>>,
I>>>
pu
Setting value as per unit value.
Setting done in xIn
DT
Operation charact./ definite
time (I>)
Curve
NI, VI
EI, LTI
Operation charact./ inverse
time (I>)
t>, t>>,
t>>>
s Operation
time
Setting
values
k
Time multiplier at inverse time
(I>)