SERVICE
SERVICE
Relays
Relays
Force:OFF
Force:ON
T1: 0
Off
0
On
1
I
I
I
I
I
I
I I
I
I
I
I
I
I
I
I
I
I
I
I
I I
I
I
I
I
I
I
I
I
I
I
I
I
I I
I
I
I
I
I
I
I
I
I
I
I
I
I I
I
I
I
I
I
I
Figure 4.4-1 Activation of the Force function.
5. Push the ENTER key while on the Force: level to be able to
change the setting (the parameter to be set is blinking)
6. Push the UP and DOWN keys to change the OFF text to the
ON text in the display (Force function activated).
7. Push the ENTER key to confirm the setting and to move
back to the Force: level
8. The Force: level has a selection list. Push the UP and DOWN
keys to select the desired output relay, which is controlled on
and off by forced control:
9. Push the ENTER key to obtain the setting state, e.g.
Relays/T1.
10. Push the UP or DOWN key to change the selection 0 -> 1.
11. Push the ENTER key to perform a controlled operation of
the output relay (e.g. the T1 is activated) and to return to
the Force: level.
12. Push the LEFT key for more than 2 s to return from the
Force: setting state to the normal Force: state without
changing the control state.
13. Push the LEFT key to return from the Force: setting state to
the Relays submenu.
14. Push the LEFT key to return to the main menu.
4.5.
Setting range limits
Note!
If parameters requiring a setting value are given out-of-range
settings, a fault message will be obtained when the setting is
confirmed with the ENTER key. Adjust the setting to within the
allowed setting range.